AC keeps tripping the breaker

A breaker that trips when the AC runs is protecting the wiring from too much current. The usual culprits are a failing capacitor or a compressor drawing excess current at startup, a shorted fan motor, or a loose or corroded connection. Reset it once. If it trips again, leave it off and call, because repeated resets can damage the compressor and the wiring.

Leave it off if…

Turn the system off and call a technician if:

  • The breaker trips again after one reset. Leave it off.
  • You smell burning, or see scorch marks at the outdoor disconnect, the breaker panel or the unit.
  • The breaker or the panel cover feels hot.
  • The outdoor unit hums or buzzes loudly without starting.

One careful reset

A breaker is a safety device. One reset tells you something; resetting it again and again can damage the system, or worse.

  1. Turn the thermostat to Off before resetting the breaker.

    Restarting the compressor immediately after a trip is hard on it.

  2. Reset the breaker once by pushing it fully off, then on, and wait about five minutes before calling for cooling.

    Gives the system's pressures time to settle before the compressor starts.

  3. With the power off, clear grass, leaves and debris from around the outdoor unit.

    Restricted airflow makes the unit work harder.

  4. Note when the trip happens: at startup, after it runs a while, or during storms.

    The timing tells the technician a lot about the cause.

What that breaker protects

The outdoor unit and the air handler are usually on separate breakers. Which one trips is the first clue.

How a split air-conditioning system worksSchematic: inside the house, an air handler with an evaporator coil and blower cools indoor air; a thermostat on the wall controls it; a condensate drain carries water away from the coil. Two copper refrigerant lines, the line set, run through the wall to the outdoor condenser, where the compressor and condenser coil release the heat outside.INSIDEOUTSIDEAIR HANDLERCONDENSER256
Parts of the diagram

The compressor draws a large surge every time it starts, and the capacitor helps it get going. A weak capacitor, a hard-starting compressor or a dirty outdoor coil all make that draw larger or longer.

More on outdoor unit

Every connection between the breaker, the disconnect and the unit carries that current. Loose, corroded or burnt ones heat up, and salt air near the coast speeds that along.

If the indoor breaker is the one tripping, the blower motor and its wiring are the place to look.

Likely causes, most common first

Pick one to see how likely it is and what it means.

Choose a likely cause

Common

Technician fix

Weak capacitor or hard-starting compressor

The run capacitor helps the compressor and fan motor start and run. As it weakens, the compressor struggles at startup and draws enough current to trip the breaker, especially on the hottest afternoons.

Occasional

Technician fix

Loose, corroded or burnt connections

Heat, vibration and humid or salty air loosen and corrode connections at the contactor, the disconnect and the breaker itself. A poor connection heats up, and the extra resistance can trip the breaker or scorch the wiring.

Occasional

Technician fix

Shorted or grounded motor or compressor

When the insulation inside a fan motor or compressor breaks down, current leaks to ground and the breaker trips immediately. This needs electrical testing to confirm before any part is replaced.

Occasional

You can check this

Dirty outdoor coil or blocked airflow outside

Grass, leaves and a matted coil make the outdoor unit run hotter at higher pressure, which raises the current it draws. Clearing debris around the unit with the power off is safe; coil cleaning is part of maintenance.

AC Maintenance

Rare

Technician fix

Worn or mismatched breaker

A breaker that has tripped many times can weaken, and a breaker must match the size listed on the unit's nameplate. Checking that takes a technician or electrician.

What gets measured

Breaker trips are confirmed with a meter before any part is replaced.

Running and starting current

amps

Compared with the ratings on the unit's data plate. A draw well above them points to the compressor, the capacitor or the outdoor coil.

Capacitor

µF

Compared with the rating printed on it. A weak capacitor makes the compressor and fan motor work harder to start.

Motor windings

ohms to ground

A compressor or fan motor shorted to ground trips the breaker every time, and resetting it never fixes that.

Connections

Checked from the breaker to the unit for heat damage, corrosion and loose terminals.

What our visit looks like

A technician measures the current the system draws at startup and while running, tests the capacitor, checks the compressor and fan motor windings for shorts to ground, and inspects every connection from the breaker to the unit. The cause is confirmed before parts are replaced. Free service call with repair.

Questions

Is it safe to keep resetting the AC breaker?

No. Reset it once at most. A breaker that trips again is telling you something is drawing too much current or has a fault. Repeated resets can overheat wiring and damage the compressor, which is the most expensive part of the system.